Class ANSI | 56-1 | 56-2 | 56-3 | 56-4 | 56-5 | |
H | 146 | 165 | 191 | 241 | 318 | |
h | 50.8 | 50.8 | 50.8 | 50.8 | 63.5 | |
Main dimension(mm) | D | 191 | 228 | 267 | 305 | 343 |
d | 34.9 | 34.9 | 34.9 | 34.9 | 34.9 | |
R1 | 19 | 19 | 19 | 19 | 19 | |
R2 | 14 | 14 | 14 | 14 | 14 | |
Leakage distance/in | 12 | 17 | 21 | 27 | 34 | |
Dry arcing distance/in | 7 | 8 | 9 | 11 | 14 | |
Power frequency-Dry/kV | 95 | 110 | 125 | 140 | 175 | |
Power frequency-Wet/kV | 60 | 70 | 80 | 95 | 125 | |
Puncture voltage | 130 | 145 | 165 | 185 | 225 | |
Critical impulse-Positive/kV | 150 | 175 | 200 | 225 | 270 | |
Critical impulse-negative/kV | 190 | 225 | 265 | 310 | 340 | |
Radio influence voltage-test voltage to ground/kV | 15 | 22 | 30 | 30 | 44 | |
Radio influence voltage-maximum RIV at 1000Hz-uV-plain | 8000 | 12000 | 16000 | 16000 | 25000 | |
Radio influence voltage-maximum RIV at 1000Hz-uV-radio freed | 100 | 100 | 200 | 200 | 200 | |
Cantilever strength /lb | 2500 | 3000 | 3000 | 3000 | 3000 |